Accumulation and transport of microbial-size particles in a pressure protected model burn unit: CFD simulations and experimental evidence.

Background: Controlling airborne contamination is of major importance in burn units because of the high susceptibility of burned patients to infections and the unique environmental conditions that can accentuate the infection risk. In particular the required elevated temperatures in the patient room...

Descripción completa

Detalles Bibliográficos
Publicado en:BMC Infectious Diseases Vol. 11; no. 1; pp. 58 - 59
Autores principales: Beauchêne, Christian, Laudinet, Nicolas, Choukri, Firas, Rousset, Jean-Luc, Benhamadouche, Sofiane, Larbre, Juliette, Chaouat, Marc, Benbunan, Marc, Mimoun, Maurice, Lajonchère, Jean-Patrick, Bergeron, Vance, Derouin, Francis
Formato: research Journal Article
Publicado: BioMed Central 2011
Acceso en línea:Ver este registro en EBSCOhost
fields @attributes:
  recordID: 1
pdfLink:
plink: https://search.ebscohost.com/login.aspx?direct=true&db=ccm&AN=104847148&site=ehost-live
header:
  @attributes:
    shortDbName: ccm
    uiTerm: 104847148
    longDbName: CINAHL Complete
    uiTag: AN
  controlInfo:
    bkinfo:
    dissinfo:
    jinfo:
      jid:
        14712334
        1CHU
      jtl: BMC Infectious Diseases
      issn: 14712334
      maglogo: N
    pubinfo:
      dt: 2011
      vid: 11
      iid: 1
      pid: 24147
      pub: BioMed Central
    artinfo:
      ui:
        104847148
        104847148
        NLM21371304
        2010980351
        10.1186/1471-2334-11-58
        NLM21371304
        PMC3056797
        104847148
      ppf: 58
      ppct: 1
      formats:
      tig:
        atl: Accumulation and transport of microbial-size particles in a pressure protected model burn unit: CFD simulations and experimental evidence.
      aug:
        au:
          Beauchêne, Christian
          Laudinet, Nicolas
          Choukri, Firas
          Rousset, Jean-Luc
          Benhamadouche, Sofiane
          Larbre, Juliette
          Chaouat, Marc
          Benbunan, Marc
          Mimoun, Maurice
          Lajonchère, Jean-Patrick
          Bergeron, Vance
          Derouin, Francis
        affil: Laboratory of Parasitology-Mycology, Saint-Louis hospital, Assistance Publique-Hôpitaux de Paris, and University Paris, Diderot, France. francis.derouin@sls.aphp.fr.
      sug:
        subj:
          Air Microbiology
          Biomedical Engineering Methods
          Burn Units
          Particulate Matter Analysis
          Atmospheric Pressure
          Computer Simulation
          France
          Risk Assessment
      ab: Background: Controlling airborne contamination is of major importance in burn units because of the high susceptibility of burned patients to infections and the unique environmental conditions that can accentuate the infection risk. In particular the required elevated temperatures in the patient room can create thermal convection flows which can transport airborne contaminates throughout the unit. In order to estimate this risk and optimize the design of an intensive care room intended to host severely burned patients, we have relied on a computational fluid dynamic methodology (CFD).Methods: The study was carried out in 4 steps: i) patient room design, ii) CFD simulations of patient room design to model air flows throughout the patient room, adjacent anterooms and the corridor, iii) construction of a prototype room and subsequent experimental studies to characterize its performance iv) qualitative comparison of the tendencies between CFD prediction and experimental results. The Electricité De France (EDF) open-source software Code_Saturne® (http://www.code-saturne.org) was used and CFD simulations were conducted with an hexahedral mesh containing about 300 000 computational cells. The computational domain included the treatment room and two anterooms including equipment, staff and patient. Experiments with inert aerosol particles followed by time-resolved particle counting were conducted in the prototype room for comparison with the CFD observations.Results: We found that thermal convection can create contaminated zones near the ceiling of the room, which can subsequently lead to contaminate transfer in adjacent rooms. Experimental confirmation of these phenomena agreed well with CFD predictions and showed that particles greater than one micron (i.e. bacterial or fungal spore sizes) can be influenced by these thermally induced flows. When the temperature difference between rooms was 7°C, a significant contamination transfer was observed to enter into the positive pressure room when the access door was opened, while 2°C had little effect. Based on these findings the constructed burn unit was outfitted with supplemental air exhaust ducts over the doors to compensate for the thermal convective flows.Conclusions: CFD simulations proved to be a particularly useful tool for the design and optimization of a burn unit treatment room. Our results, which have been confirmed qualitatively by experimental investigation, stressed that airborne transfer of microbial size particles via thermal convection flows are able to bypass the protective overpressure in the patient room, which can represent a potential risk of cross contamination between rooms in protected environments.
      pubtype: Academic Journal
      doctype:
        research
        Journal Article
      ougenre: Article
    language: English
    refInfo:
    holdings:
      @attributes:
        islocal: N